At a glance:
- Well-proven temperature measurement
- Pt100 element, accuracy class A according to IEC 60751
- Measuring ranges –50 °C … +150 °C and –50 °C … +250 °C
- Various mechanical adaptations and insertion lengths
- Pt100 (4-wire) or 4 mA … 20 mA (2-wire)
- Reliable operation through rugged design and high-quality materials
Technical data:
- Measuring range: –50 °C +150 °C/ –50 °C +250 °C
- Accuracy of sensor element: Class A according to IEC 60751
- Accuracy of the opt. measuring transducer: ≤ ± 0.1 % of span
- Signal outputs and maximum ohmic load RA: Pt100, 4-wire, 4 mA … 20 mA, 2-wire (RA ≤ (L+ – 10 V) / 0.028 A [Ohm])
- Electrical connection: Cable gland M16 x 1.5, IP65/ Cable gland M16 x 1.5, IP67
Dimensions:
Connection diagram: