IPAQ C310RTD INOR is Programmable 2-wire transmitter for RTD and Resistance inputs; Type: Head-mounted; Input: RTD, ohm, RTD: Pt100, Pt10 … Pt1000, Ni100, Ni120, Ni1000; Output: 4-20 mA; Wireless communication: NFC and Bluetooth®
| Type | Head-mounted |
| Input | RTD, ohm: – RTD: Pt100, Pt10 … Pt1000, Ni100, Ni120, Ni1000 |
| Type of transmitter | Digital |
| Output | 4-20 mA |
| Measuring range | Pt100 (IEC 60751, α=0.00385) -200 to +850 °C / -328 to +1562 °F Pt X (10 ≤ X ≤ 1000) (IEC 60751, α=0.00385) -200 to +850 °C / -328 to +1562 °F Pt100 (JIS C 1604, α=0.003916) -200 to +850 °C / -328 to +1562 °F Ni100 (DIN 43760) -60 to +250 °C / -76 to +482 °F Ni120 (Edison Curve No. 7) -60 to +250 °C / -76 to +482 °F Ni1000 (DIN 43760) -50 to +180 °C / -58 to +356 °F |
| Sensor error | NAMUR, NE 43 |
| Adjustments – Zero point | Any value within range limits |
| Adjustments – Minimum span | – RTD: 10 °C – Resistance: 10 Ω |
| Ambient temperature | -40 to +85 °C / -40 to +185 °F |
| Humidity | 0…98% RH (non-condensing) |
| Vibration | IEC 60068-2-6, 10g |
| EMC | EN 61326-1, EN 61326-2-3, EN 61000-6-2, EN 61000-6-4, NAMUR NE 21 |
| Isolation | 1500 VAC, 1 min |
| Power supply | 8 to 36 VDC |
| Long-term stability | Max. drift ±0,02% of span/year |
| Typical accuracy | Max. of ±0.1 °C or ±0.1 % of span |
| Adjustable filtering level | 0.17…90 s for 3-wire RTD |
| Configuration | ConSoft or INOR Connect |
| Wireless communication | NFC and Bluetooth® * |