UB40.241 PULS is DC-UPS control unit; DC output: DC 24 V/ 40 A; Input: DC 24 V (± 25 %); Dimensions (WxHxD): 46 x 124 x 127 mm
| Input | |
| DC Input voltage | DC 24 V (± 25 %) |
| Int. current consumption (incl. charging current) | 3.2 / 6.2 A |
| Output data | |
| Nominal voltage | 24 Vdc |
| Output current | 40 A |
| Output power | 960 W |
| Buffering | |
| Storage element | External lead acid battery |
| Allowed battery size | 12 Ah – 200 Ah |
| Temperature tracking of the end-of-charge voltage | automatically with temp. sensor |
| Overview | |
| Dimensions (WxHxD) | 46 mm x 124 mm x 127 mm |
| Weight per unit (excl. packaging) | 530 g |
| Operating temp. range | -25 °C to 70 °C |
| Connection method | Screw terminals |
| DC-OK signal | No |
| Special feature | for battery sizes from 12Ah to 200Ah |