Alarm Unit SR361 INOR; Alarm Unit with Current and Voltage Input and Double Relay Outputs; Current and voltage input; SPDT relays with 6 A switch capacity; Typical accuracy: Trip point: ±0,2 % of span
| Input Current | 0(4) to 20 mA |
| Input impedance | 5 Ω |
| Maximum overload | 200 mA |
| Input Voltage | 0(2) to 10 V |
| Input impedance | 120 kΩ |
| Maximum overload | 300 V |
| 2-wire Transmitter Supply +Us | 16 V at UPower = 24 V, (13 … 22 V depending on the supply voltage) current limited ≤ 30 mA |
| Output, Relay 1 & 2 | |
| Relay contacts | 1-pole switch over contact (SPDT) |
| Contact rating max. | AC: 250 V / 6 A, 1500 VA DC: 250 V / 0.2 A, 115 V / 0.3 A, 30 V / 6 A |
| Relay function | Monostable, Normally active or passive (switch selectable) |
| Alarm functions, relay 1 & 2 | High/Low alarm (switch selectable) |
| Alarm indication | Alarm state indicated by yellow LED |
| Response time | approx. ca. 20 ms |
| Operation temperature | -20 to +60 °C / -4 to +140 °F |
| Galvanic isolation | |
| Input / power supply / relay outputs | 4 kVAC, 1 min |
| Relay 1 / Relay 2 | 3 kVAC, 1 min |
| Power supply | |
| Voltage | 24 VAC/DC ±15 %, 48 to 62 Hz (AC supply). 24 V CD, ± 15 %, 1.0 W |
| Typical accuracy | Trip point: ±0.2 % of span |
| Mounting | 35 mm DIN rail acc. to EN 60715 |