Isolators IsoPAQ-632 INOR; Signal Splitter/Repeater with double outputs for mA and V signals; No. Of channels: 2 channels; Isolation level: 3 kV; Typical accuracy: 0,1% FS; Working voltage: 600 VAC/DC
Online support

Isolators IsoPAQ-632 INOR; Signal Splitter/Repeater with double outputs for mA and V signals; No. Of channels: 2 channels; Isolation level: 3 kV; Typical accuracy: 0,1% FS; Working voltage: 600 VAC/DC

Input
Input signal
(calibrated switchable)
0 … 20 mA,  0 … 10 V,   0 … 5 V
4 … 20 mA,  2 … 10 V,  1 … 5 V
Input resistance Current input: ≤ 35 Ω
Voltage input: ≥ 100 kΩ
Overload Current input: < 50 mA
Voltage input: < 30 V
Transmitter supply Tx 16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA)
Output I / Output II
Output signal
(calibrated switchable)
0 … 20 mA,  0 … 10 V,  0 … 5 V
4 … 20 mA,  2 … 10 V,  1 … 5 V
Load Current output: ≤ 6 V (300 Ω at 20 mA)
Voltage output: ≤ 5 mA (2 kΩ at 10 V)
Linear transmission range –1 … +110 %
Residual ripple < 10 mVrms
Transmission error < 0.1 % full scale
Temperature coefficient < 100 ppm/K
Cut-off frequency -3 dB -3 dB 5 kHz
Response time T99 150 µs
Test voltage 3 kV AC, 50 Hz, 1 min.
Input against Output 1 against Output 2 against power supply
Ambient temperature Operation: – 25 °C to + 70 °C (– 13 to + 158 °F)
Transport and storage: – 40 °C to + 85 °C (– 40 to + 185 °F)
Power supply 24 V DC voltage range 16.8 … 31.2 V DC, approx. 1.4 W
EMC EN 61326-1
Construction 62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
Weight Approx. 70 g

🔗 View all INOR products at AUMI »»»

🔗 Official INOR website »»»

At a glance

  • Signal Splitter/Repeater with double outputs for mA and V signals
  • The Signal Splitter/Repeater IspPAQ-632 is used for isolation, conversion and distribution of 0/4 … 20 mA, 0/1 … 5 V and 0/2 … 10 V standard signals. The measuring input can also supply the loop power for 2-wire transmitters.
  • The input and two isolated outputs can be easily configured by using DIP switch. Due to the calibrated range selection no further adjustment is necessary.
  • The auxiliary power can be supplied via the connection terminals or via the optional In-Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.

Features

  • Calibrated signal setting via DIP switch: Input and outputs can be set by using DIP switch – high precision
    without any further adjustment
  • 4-Port isolation: Protection against erroneous measurements due to parasitic voltages or ground loops
  • Extremely slim design: 6.2 mm slim housing for a simple and space saving DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector: Allows for fast and economical installation
  • Protective Separation acc. to EN 61140: Protects service personnel and downstream devices against impermissibly high voltage

No documents available

guest

Oldest
Newest
Inline Feedbacks
View all comments
Contact Contact AUMI
Zalo Mess Phone Location