- Type: Rail-mounted
- Input: RTD; Thermocouple; Universal
- Input RTD: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input Thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Type Of Transmitter: Digital
- Output: 4-20 mA; HART®
- Isolation: Isolated
- Measuring channels: 2 channels
- Sensor connection: 2-, 3-, 4-wire connection
- Power supply: IPAQ R520/R520S: 10 to 36 VDC; IPAQ R520X/R520XS: 10 to 30 VDC
- Approvals: ATEX, IECEx, SIL2
- Typical accuracy: RTD: Max. of ±0.1 °C or ±0,05 % of span; TC: Typical: ±0.05 of span
2-wire transmitter IPAQ R520
- Type: Rail-mounted
- Input: RTD; Thermocouple; Universal
- Input RTD: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input Thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Output: 4-20 mA; HART®
- Isolation: Isolated
- Measuring channels: 2 channels
- Sensor connection: 2-, 3-, 4-wire connection
- Approvals: ATEX, IECEx, SIL2
Category: 2-wire Transmitters
At a glance:
- HART Compatible Universal Dual-input 2-wire Transmitters
- The IPAQ R520 transmitters are universal, isolated, dual-input temperature transmitters with additional voltage and resistance input. The R520N is approved for Non-Incendive use in Ex-Zone 2. R520X/R520XS are Intrinsically Safe versions for use in Ex-Zone 1 and 2. The transmitters are compatible with the HART 6 protocol. Typical characteristics are the high accuracy, stability and reliability combined with a robust housing.
- Universal, dual-input for RTD and T/C
- SIL 2 compatible according to IEC 61508-2
- 5 year guaranted stability
- Withstands 10 g vibrations
- Complies with NAMUR NE 21, NE 43, NE 53, NE 89 and NE 107
- EMC immunity according to Criteria A
- Sensor Backup
- Sensor Drift Monitoring
- Sensor Isolation Monitoring
- Sensor Matching
- 50 point customized linearization
- Integrated in Emerson AMS and Siemens PDM systems
Technical data:
- Type: Rail-mounted
- Input: RTD; Thermocouple; Universal
- Input RTD: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input Thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Type Of Transmitter: Digital
- Output: 4-20 mA; HART®
- Isolation: Isolated
- Measuring channels: 2 channels
- Sensor connection: 2-, 3-, 4-wire connection
- Power supply: IPAQ R520/R520S: 10 to 36 VDC; IPAQ R520X/R520XS: 10 to 30 VDC
- Approvals: ATEX, IECEx, SIL2
- Typical accuracy: RTD: Max. of ±0.1 °C or ±0,05 % of span; TC: Typical: ±0.05 of span
Dimensions:
Connection diagram:
You can download more at the document here: Download
Related products
2-wire Transmitters
- Type: Head-mounted
- Input RTD: Pt100, Pt1000
- Output: 0-10 V
- Isolation: Unisolated
- Measuring channels: 1 channel
- Input connections: 3-wire connection
- Power supply: 15 to 30 VDC
2-wire Transmitters
- Type: Head mounted
- Input: Pt100, Pt1000
- Type of transmitter: Digital
- Output: 4-20 mA
- Measuring range: –200…+850 °C / -328…+1562 °F
- Typical accuracy: Max. ±0,15 K or ±0,15 % of span
- Configuration: App INOR Connect*
- Wireless communication: NFC®
2-wire Transmitters
- Type: Rail-mounted
- Input: RTD, TC, mV, ohm
- Input RTD: Pt100, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Output: 4-20 mA
- Galvanic isolation: 1500 VAC
- Measuring channels: 1 channel
- Sensor connection: 2-, 3-, 4-wire connection
2-wire Transmitters
- Type: Head-mounted
- Input: RTD, TC, mV, ohm
- Input RTD: Pt100, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Output: 4-20 mA, HART protocol
- Galvanic isolation: 1500 VAC
- Measuring channels: 1 channel
- Sensor connection: 2-, 3-, 4-wire connection
2-wire Transmitters
- Type: Head-mounted
- Input: RTD, TC, mV, ohm
- Input RTD: Pt100, Pt1000, Ni100, Ni120, Ni1000, Cu10
- Input thermocouple: Type B, C, D, E, J, K, N, R, S, T
- Output: 4-20 mA
- Galvanic isolation: 1500 VAC
- Measuring channels: 1 channel
- Sensor connection: 2-, 3-, 4-wire connection
- Power supply: IPAQ-C330: 8 to 36 VDC/ IPAQ-C330X: 8 to 30 VDC