- Input
Input signal (calibrated switchable): 0 … 20 mA, 0 … 10 V, 0 … 5 V/ 4 … 20 mA, 2 … 10 V, 1 … 5 V
Input resistance: Current input: ≤ 35 Ω/ Voltage input: ≥ 100 kΩ
Overload: Current input: < 50 mA/ Voltage input: < 30 V
Transmitter supply Tx: 16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA)
- Output I / Output II
Output signal (calibrated switchable): 0 … 20 mA, 0 … 10 V, 0 … 5 V/ 4 … 20 mA, 2 … 10 V, 1 … 5 V
Load: Current output: ≤ 6 V (300 Ω at 20 mA)/ Voltage output: ≤ 5 mA (2 kΩ at 10 V)
Linear transmission range: –1 … +110 %
Residual ripple: < 10 mVrms
- General Data
Transmission error: < 0.1 % full scale
Temperature coefficient: < 100 ppm/K
Cut-off frequency -3 dB: -3 dB 5 kHz
Response time T99: 150 µs
Test voltage: 3 kV AC, 50 Hz, 1 min. Input against Output 1 against Output 2 against power supply
Working voltage (Basic Insulation): 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection against electrical shock: Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature: Operation: – 25 °C to + 70 °C (– 13 to + 158 °F)/ Transport and storage: – 40 °C to + 85 °C (– 40 to + 185 °F)
Power supply: 24 V DC voltage range 16.8 … 31.2 V DC, approx. 1.4 W
EMC: EN 61326-1
Construction: 62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
Weight: Approx. 70 g